1SP0351 Optical Gate Driver for Press-Pack IGBTs | Power Integrations
The 1SP0351 serves 4500 V press-pack IGBTs used in equipment such as VSC-HVDC converters and STATCOMs. Power Integrations lists modules from Toshiba, Westcode and ABB. Select the board against the actual press-pack device.
Driving a press-pack switch in a grid converter
The 1SP0351 serves 4500 V press-pack IGBTs used in equipment such as VSC-HVDC converters and STATCOMs. Power Integrations lists modules from Toshiba, Westcode and ABB. Select the board against the actual press-pack device.
An optical interface carries the control signal, while the built-in DC/DC converter provides basic isolation. Its ±50 A peak gate current and 1.8 W output power at maximum ambient describe separate limits on a repetitive switching waveform.
Dynamic Advanced Active Clamping uses voltage-slew feedback during turn-off. The published extended DC-link window applies to the off state for up to 60 seconds, a distinct condition to account for in the converter operating sequence.
Key Features
- Clamp feedbackVoltage slew rate during turn-off
- Supply constructionBuilt-in DC/DC with basic isolation
Target Applications
- VSC-HVDC, FACTS and STATCOM press-pack converter stages
Compare 1SP0351 Variants
Comparison of 10 selected variants from Power Integrations
| Parameter | 1SP0351V2D0C-TG2000SW45ZC-P200 | 1SP0351V2D0C-T2000BB45G | 1SP0351V2D0C-P2000DL45X168 | 1SP0351V2C0C-TG2000SW45ZC-P200 | 1SP0351V2C0C-T2000BB45G | 1SP0351V2C0C-P2000DL45X168 | 1SP0351V2B0C-5SNA3000K452300 | 1SP0351V2B0C-5SNA2000K452300 | 1SP0351V2A0C-5SNA3000K452300 | 1SP0351V2A0C-5SNA2000K452300 |
|---|---|---|---|---|---|---|---|---|---|---|
| Conformal Coated | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
| Connection Type to Igbt | Cable | Cable | Cable | Cable | Cable | Cable | Cable | Cable | Cable | Cable |
| Driving Mode | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent | Direct-Independent |
| Gate Turn Off Voltage | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V | --9.4 V |
| Gate Turn on Voltage | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V | +15.0 V |
| Igbt Manufacturer | CRRC | IXYS UK Westcode | Infineon | CRRC | IXYS UK Westcode | Infineon | ABB | ABB | ABB | ABB |
| Igbt Voltage Class | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V | 4500 V |
| Interface Type | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic | Fiber Optic |
| Isolation Technology | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic | Galvanic |
| Isolation Type | Basic | Basic | Basic | Basic | Basic | Basic | Basic | Basic | Basic | Basic |
| Max Gate Peak Current | +50 A | +50 A | +50 A | +50 A | +50 A | +50 A | +50 A | +50 A | +50 A | +50 A |
| Max Switching Frequency | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz | 2.0 kHz |
| Module Housing | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack | Press-Pack |
| Number of Channels | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 | 1 |
| Paralleling Support | No | No | No | No | No | No | No | No | No | No |
| Power Output Channel Max | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W | 1.8 W |
| Product Family | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 | 1SP0351 |
| Protection Features | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) | Dynamic Adv Active Clamping, Over-voltage, Short Circuit, UVLO(Sec-side), UVLO(Pri-side) |
| Roms | No | No | No | No | No | No | No | No | No | No |
| Supply Voltage Typ | 15 V | 15 V | 15 V | 15 V | 15 V | 15 V | 15 V | 15 V | 15 V | 15 V |
| Supported Module S | TG2000SW45ZC-P200 | T2000BB45G | P2000DL45X168 | TG2000SW45ZC-P200 | T2000BB45G | P2000DL45X168 | 5SNA3000K452300 | 5SNA2000K452300 | 5SNA3000K452300 | 5SNA2000K452300 |
| Supported Module Type | IGBT | IGBT | IGBT | IGBT | IGBT | IGBT | IGBT | IGBT | IGBT | IGBT |
| Supported Topologies | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped | 2-level Voltage Source, 3-level NP-Clamped - Type 1, 3-level NP-Clamped - Type 2, Multi-Level NP-Clamped |
| Technology | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 | SCALE-2 |
| Ul Compliant | compliant | compliant | compliant | compliant | compliant | compliant | compliant | compliant | compliant | compliant |
| Voltage Dc Link Off State 60s | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V | 4000 V |
| Request Quote | Request Quote | Request Quote | Request Quote | Request Quote | Request Quote | Request Quote | Request Quote | Request Quote | Request Quote |
Base Numbers
MPN counts describe each base number’s catalog coverage; they are not a series total.
| Base Number | Description | Variants | Action |
|---|---|---|---|
| 1SP0351V2A0 | 1SP0351V2A0 variants from Power Integrations | 2 MPNs | View Details |
| 1SP0351V2B0 | 1SP0351V2B0 variants from Power Integrations | 2 MPNs | View Details |
| 1SP0351V2C0 | 1SP0351V2C0 variants from Power Integrations | 3 MPNs | View Details |
| 1SP0351V2D0 | 1SP0351V2D0 variants from Power Integrations | 3 MPNs | View Details |
Technical Specifications
Driving a press-pack switch in a grid converter
1SP0351 Series Applications
Frequently Asked Questions
Common technical questions about the 1SP0351 series.